6kV&10kV Oil-Immersed Transformer

 
6kV and 10kV oil-immersed distribution transformers are important equipment in the distribution network and power supply and distribution systems of industrial & mining enterprises. They are widely used in industrial & mining enterprises, agriculture and civil architectures. They are also popular in sites with oil contamination and chemical substances.

Product introduction



Working Conditions:
No.
Conditions
Units
Parameter Values
1
Pollution Grade
 
IV
2
Ambient Temperature
Maximum Daily Temperature
40
Minimum Daily Temperature
-45
Maximum Daily Temperature Difference
K
25
Average Temperature of the Hottest Month
30
Maximum Annual Average Temperature
20
3
Humidity
Average Daily Relative Humidity
%
≤95
Average Monthly Relative Humidity
≤90
4
Altitude
m
1000
5
Solar Radiation Intensity
W/cm2
0.1
6
Maximum Icing Thickness
mm
10
7
Maximum average wind speed: keeping in good conditions for 10min at 10m from the ground level
m/s
35
8
Earthquake Resistance
Horizontal Ground Acceleration
m/s2
2
Safety Coefficient of 3 Since Resonance Cycles
 
≥1.67
9
Installation Site
 
Outdoor
Note 1: Working conditions in high altitude regions (above 1000m) must be adjusted in conformity with Q/GDW 13001-2014 (High Altitude External Insulation Configuration Technical Specification).


Product Parameters:
Table 1  6kV & 10kV - 30kV.A ~ 2 500 kV.A, Three-Phase Duplex Windings, No-Load Voltage Regulation, Distribution Transformer (S11 Series)
Rated Capacity (KV.A)
Voltage Combination & Tapping Range
Connection Symbol
No-Load Loss (kW)
On-Load Loss (kW)
No-Load Current (%)
Short-Circuit Impedance (%)
High Voltage (kV)
High Voltage Tapping Range (%)
Low Voltage (kV)
30
6
6.3
10
10.5
±2×2.5
±5
0.4
Dyn11
Yzn11
Yyn0
0.100
0.630/0.600
1.5
4.0
50
0.130
0.910/0.870
1.3
63
0.150
1.09/1.04
1.2
80
0.480
1.31/1.25
1.2
100
0.200
1.58/1.50
1.1
125
0.240
1.89/1.80
1.1
160
0.280
2.31/2.20
1.0
200
0.340
2.73/2.60
1.0
250
0.400
3.20/3.05
0.90
315
0.480
3.83/3.65
0.90
400
0.570
4.52/4.30
0.80
500
0.680
5.41/5.15
0.80
630
Dyn11
Yyn0
0.810
6.20
0.60
4.5
800
0.980
7.50
0.60
1 000
1.15
10.3
0.60
1 250
1.36
11.0
0.50
1 600
1.64
14.0
0.50
2 000
1.94
18.3
0.40
5.0
2 500
2.29
21.2
0.40
Note 1: If the rated capacity is 500kV.A or below, the data of “On-Load Loss” on the left of slash (/) is for Dyn11 or Yzn11, on the right for Yyn0.
Note 2: If transformers’ annual average load rate is between 35% and 40%, using loss values in this Table can obtain the highest operating efficiency. 


Table 2  6kV & 10kV - 630kV.A ~ 6 300 kV.A, Three-Phase Duplex Windings, No-Load Voltage Regulation, Power Transformer (S11 Series)
Rated Capacity (KV.A)
Voltage Combination & Tapping Range
Connection Symbol
No-Load Loss (kW)
On-Load Loss (kW)
No-Load Current (%)
Short-Circuit Impedance (%)
High Voltage (kV)
High Voltage Tapping Range (%)
Low Voltage (kV)
630
6
6.3
10
10.5
±4×2.5
3
3.15
6.3
Yd11
Dy11
0.820
6.92
0.60
5.5
800
1.00
8.46
0.60
1 000
1.18
9.91
0.60
1 250
1.40
11.7
0.50
1 600
1.68
14.1
0.40
2 000
2.01
16.6
0.40
2 500
2.37
19.6
0.40
3 150
2.80
23.0
0.40
4 000
3.15
6.3
3.45
27.3
0.40
5 000
4.10
31.3
0.40
6 300
4.89
35.0
0.40
Note: If transformers’ annual average load rate is between 35% and 40%, using loss values in this Table can obtain the highest operating efficiency. 


Table 3  6kV&10kV-200kV.A~2 500 kV.A, Three-Phase Duplex Windings, On-Load Voltage Regulation, Distribution Transformer (SZ11 Series)
Rated Capacity (KV.A)
Voltage Combination & Tapping Range
Connection Symbol
No-Load Loss (kW)
On-Load Loss (kW)
No-Load Current (%)
Short-Circuit Impedance (%)
High Voltage (kV)
High Voltage Tapping Range (%)
Low Voltage (kV)
200
6
6.3
10
10.5
±4×2.5
0.4
Dyn11
Yyn0
0.380
2.90
1.0
4.0
250
0.440
3.42
0.90
315
0.530
4.10
0.90
400
0.640
4.95
0.80
500
0.760
6.89
0.80
630
0.960
7.26
0.60
4.5
800
1.12
8.89
0.60
1 000
1.36
10.4
0.60
1 250
1.56
12.3
0.50
1 600
1.92
14.7
0.50
2 000
2.27
18.6
0.40
5.0
2 500
2.68
21.6
0.40
Note: If transformers’ annual average load rate is between 35% and 40%, using loss values in this Table can obtain the highest operating efficiency. 


Table 4  6kV & 10kV-S12, S13, S14, SH16 Series, No-Load Voltage Regulation, Distribution Transformer, List of No-Load Loss & On-Load Loss
Rated Capacity (kV.A)
S12 Series
S13 Series
S14 Series
SH16 Series (Amorphous Alloy)
No-Load Loss (kW)
On-Load Loss (kW)
No-Load Loss (kW)
On-Load Loss (kW)
No-Load Loss (kW)
On-Load Loss (kW)
No-Load Loss (kW)
On-Load Loss (kW)
30
0.090
0.630/0.600
0.080
0.630/0.600
0.080
0.505/0.480
0.033
0.565/0.540
50
0.120
0.910/0.870
0.100
0.910/0.870
0.100
0.730/0.695
0.043
0.820/0.785
63
0.130
1.09/1.04
0.110
1.09/1.04
0.110
0.870/0.830
0.050
0.980/0.935
80
0.150
1.31/1.25
0.130
1.31/1.25
0.130
1.05/1.00
0.060
1.18/1.12
100
0.170
1.58/1.50
0.150
1.58/1.50
0.150
1.26/1.20
0.075
1.42/1.35
125
0.200
1.89/1.80
0.170
1.89/1.80
0.170
1.51/1.44
0.085
1.70/1.62
160
0.240
2.31/2.20
0.200
2.31/2.20
0.200
1.85/1.76
0.100
2.08/1.98
200
0.280
2.73/2.60
0.240
2.73/2.60
0.240
2.18/2.08
0.120
2.45/2.34
250
0.340
3.20/3.05
0.290
3.20/3.05
0.290
2.56/2.44
0.140
2.88/2.74
315
0.410
3.83/3.65
0.340
3.83/3.65
0.340
3.06/2.92
0.170
3.44/3.28
400
0.490
4.52/4.30
0.410
4.52/4.30
0.410
3.61/3.44
0.200
4.07/3.87
500
0.580
5.41/5.15
0.480
5.41/5.15
0.480
4.33/4.12
0.240
4.87/4.63
630
0.690
6.20
0.570
6.20
0.570
4.96
0.320
5.58
800
0.840
7.50
0.700
7.50
0.700
6.00
0.380
6.75
1 000
0.990
10.3
0.830
10.3
0.830
8.24
0.450
9.27
1 250
1.17
12.0
0.970
12.0
0.970
9.60
0.530
10.8
1 600
1.41
14.5
1.17
14.5
1.17
11.6
0.630
13.0
2 000
1.75
18.3
1.55
18.3
1.55
14.6
0.750
16.4
2 500
2.06
21.2
1.83
21.2
1.83
16.9
0.900
19.0
Note: The data of “On-Load Loss” on the left of slash (/) is for Dyn11 or Yzn11, on the right for Yyn0.

Address: No.1, West Xuefu Road, Longling Industrial Park, Gaoxin District, Yiyang City, Hunan Province, 413000, China

Contact No.: 0737-2222100

QQ: 3013508896

E-mail: huaxiangbyq@163.com

©2018 All Rights Reserved by Huaxiang Xiangneng Technology Co., Ltd.     京ICP证000000号