Products and Services
No.
|
Conditions
|
Units
|
Parameter Values
|
|
1
|
Pollution Grade
|
|
IV
|
|
2
|
Ambient Temperature
|
Maximum Daily Temperature
|
℃
|
40
|
Minimum Daily Temperature
|
-45
|
|||
Maximum Daily Temperature Difference
|
K
|
25
|
||
Average Temperature of the Hottest Month
|
℃
|
30
|
||
Maximum Annual Average Temperature
|
20
|
|||
3
|
Humidity
|
Average Daily Relative Humidity
|
%
|
≤95
|
Average Monthly Relative Humidity
|
≤90
|
|||
4
|
Altitude
|
m
|
1000
|
|
5
|
Solar Radiation Intensity
|
W/cm2
|
0.1
|
|
6
|
Maximum Icing Thickness
|
mm
|
10
|
|
7
|
Maximum average wind speed: keeping in good conditions for 10min at 10m from the ground level
|
m/s
|
35
|
|
8
|
Earthquake Resistance
|
Horizontal Ground Acceleration
|
m/s2
|
2
|
Safety Coefficient of 3 Since Resonance Cycles
|
|
≥1.67
|
||
9
|
Installation Site
|
|
Outdoor
|
|
Note 1: Working conditions in high altitude regions (above 1000m) must be adjusted in conformity with Q/GDW 13001-2014 (High Altitude External Insulation Configuration Technical Specification).
|
Rated Capacity (KV.A) | Voltage Combination & Tapping Range | Connection Symbol | No-Load Loss (kW) | On-Load Loss (kW) | No-Load Current (%) | Short-Circuit Impedance (%) | ||
High Voltage (kV) | High Voltage Tapping Range (%) | Low Voltage (kV) | ||||||
50 | 35 38.5 |
±2×2.5 ±5 |
0.4 |
Dyn11 Yyn0 |
0.160 | 1.20/1.14 | 1.3 | 6.5 |
100 | 0.230 | 2.01/1.91 | 1.1 | |||||
125 | 0.270 | 2.37/2.26 | 1.1 | |||||
160 | 0.280 | 2.82/2.68 | 1.0 | |||||
200 | 0.340 | 3.32/3.16 | 1.0 | |||||
250 | 0.400 | 3.95/3.76 | 0.95 | |||||
315 | 0.480 | 4.75/4.53 | 0.95 | |||||
400 | 0.580 | 5.74/5.47 | 0.85 | |||||
500 | 0.680 | 6.91/6.58 | 0.85 | |||||
630 | 0.830 | 7.86 | 0.65 | |||||
800 | 0.980 | 9.40 | 0.65 | |||||
1 000 | 1.15 | 11.5 | 0.65 | |||||
1 250 | 1.40 | 13.9 | 0.60 | |||||
1 600 | 1.69 | 16.6 | 0.60 | |||||
2 000 | 1.99 | 19.7 | 0.55 | |||||
2 500 | 2.36 | 23.2 | 0.55 | |||||
Note 1: If the rated capacity is 500kV.A or below, the data of “On-Load Loss” on the left of slash (/) is for Dyn11, on the right for Yyn0. Note 2: If transformers’ annual average load rate is between 30% and 36%, using loss values in this Table can obtain the highest operating efficiency. |
Rated Capacity (KV.A) | Voltage Combination & Tapping Range | Connection Symbol | No-Load Loss (kW) | On-Load Loss (kW) | No-Load Current (%) | Short-Circuit Impedance (%) | ||
High Voltage (kV) | High Voltage Tapping Range (%) | Low Voltage (kV) | ||||||
630 | 35 | ±2×2.5 ±5 |
3.15 6.3 10.5 |
Yd11 | 0.830 | 7.86 | 0.65 | 6.5 |
800 | 0.980 | 9.40 | 0.65 | |||||
1 000 | 1.15 | 11.5 | 0.65 | |||||
1 250 | 1.40 | 13.9 | 0.55 | |||||
1 600 | 1.69 | 16.6 | 0.45 | |||||
2 000 | 2.17 | 18.3 | 0.45 | |||||
2 500 | 2.56 | 19.6 | 0.45 | |||||
3 150 | 35~38.5 | ±2×2.5 ±5 |
3.15 6.3 10.5 |
3.04 | 23.0 | 0.45 | 7.0 | |
4 000 | 3.61 | 27.3 | 0.45 | |||||
5 000 | 4.32 | 31.3 | 0.45 | |||||
6 300 | 5.24 | 35.0 | 0.45 | 8.0 | ||||
8 000 | 35~38.5 | ±2×2.5 | 3.15 3.3 6.3 6.6 10.5 |
YNd11 | 7.20 | 38.4 | 0.35 | |
10 000 | 8.70 | 45.3 | 0.35 | |||||
12 500 | 10.0 | 53.8 | 0.30 | |||||
16 000 | 12.1 | 65.8 | 0.30 | |||||
20 000 | 14.4 | 79.5 | 0.30 | |||||
25 000 | 17.0 | 94.0 | 0.25 | 10.0 | ||||
31 500 | 20.2 | 112 | 0.25 | |||||
Note 1: If the low voltage is 10.5kV, transformers of Dyn11 can also be supplied. Note 2: -5% is the maximum current tapping position, if the rated capacity is 3150kV.A or above. Note 3: If transformers’ annual average load rate is between 35% and 45%, using loss values in this Table can obtain the highest operating efficiency. |
Rated Capacity (KV.A) | Voltage Combination & Tapping Range | Connection Symbol | No-Load Loss (kW) | On-Load Loss (kW) | No-Load Current (%) | Short-Circuit Impedance (%) | ||
High Voltage (kV) | High Voltage Tapping Range (%) | Low Voltage (kV) | ||||||
2 000 | 35 | ±3×2.5 | 6.3 10.5 |
Ydll |
2.30 | 19.2 | 0.50 | 6.5 |
2 500 | 2.72 | 20.6 | 0.50 | |||||
3 150 | 35~38.5 | ±3×2.5 |
6.3 10.5 |
3.23 | 24.7 | 0.50 | 7.0 | |
4 000 | 3.87 | 29.1 | 0.50 | |||||
5 000 | 4.64 | 34.2 | 0.50 | |||||
6 300 | 5.63 | 36.7 | 0.50 | 8.0 | ||||
8 000 | 35~38.5 | ±3×2.5 |
6.3 6.6 10.5 |
YNdll |
7.87 | 40.6 | 0.40 | |
10 000 | 9.28 | 48.0 | 0.40 | |||||
12 500 | 10.1 | 56.8 | 0.35 | |||||
16 000 | 13.1 | 70.3 | 0.35 | |||||
20 000 | 15.5 | 82.7 | 0.35 | |||||
25 000 | 18.3 | 97.8 | 0.30 | 10.0 | ||||
31 500 | 21.8 | 116 | 0.30 | |||||
Note 1: If the low voltage is 10.5kV, transformers of Dynll can also be supplied. Note 2: -7.5% is the maximum current tapping position. Note 3: If transformers’ annual average load rate is between 35% and 45%, using loss values in this Table can obtain the highest operating efficiency. |