Products and Services
Working conditions:
1. Altitude: ≤1000m (using plateau type design if >1000m)
2. Ambient temperature: -25℃ ~ +40℃
3. Wind speed: ≤34m/s (wind pressure ≤700pa)
4. Icing thickness: ≤20mm
5. Pollution grade: Ⅱ, Ⅲ
6. IP code: IP23
7. Relative humidity: ≤85%
8. Natural ventilation area: 5m2
9. Installation site: no fire, explosion, severe pollution, chemical corrosion or severe vibration, and gradient: ≤5°
10. Normal use on ground, or on the buildings that has less than 10m of height and can bear 60 tons of pressure
Remark: please consult us if you demand other different conditions
Items
|
Units
|
High Voltage Unit
|
Transformer
|
Low Voltage Unit
|
|
40.5kV
|
12kV
|
||||
JYN, XGN, KYN
|
KYN28, XGN2, HXGN
|
SZ11, S11, SC
|
|||
Rated Voltage
|
kV
|
40.5
|
12
|
35/10-04.
|
0.4
|
Rated Capacity
|
kVA
|
|
|
≤20000
|
|
Mode of Wiring
|
|
|
|
Y, d11
|
|
Insulation Grade
|
Grade
|
|
|
F
|
|
Insulation System Temperature Limit
|
℃
|
|
|
155
|
|
Temperature Rise Limit
|
K
|
|
|
100
|
|
Rated Current (Main) Loop
|
A
|
400-1600
|
630-2000
|
|
|
Rated Short Circuit Breaking Current
|
|
25
|
31.5
|
|
|
Rated Short Circuit Making Current
|
kA
|
63
|
80
|
|
|
4s Rated Short Time Withstand Current
|
kA
|
25
|
31.5
|
|
|
Rated Peak Withstand Current
|
kA
|
63
|
80
|
|
|
Power Frequency Withstand Voltage
|
kV
|
95/118
|
42/48
|
85
|
2.0/2.5
|
Lightning Impulse Withstand Voltage
|
kV
|
185/215
|
75/85
|
185
|
8
|
Acoustic Level
|
dB
|
|
|
<55
|
|
IP Code
|
Front and four sides: IP43, ventilation part of top cover and bottom inside the box: ≥ IP23 (transformer placed in the open air: IP00)
|