This series of substation is developed based on the actual situation in China. The transformer is S11 series. Four-position load switch, two-position load switch, backup protection fuse and plug-in fuse are installed on the high voltage side. Controlling appliance, power distribution appliance, compensation device and electric energy meter are installed on the low voltage side. The transformer oil takes the role of insulation and arc-extinguishing medium. The overall substation features small volume, easy maintenance, low noise, low loss, theft prevention, high overload capacity and all-round protection. It is suitable for new-built residence communities, green belts, gardens, bus stations, wharves, hotels, construction sites and airports.
Working conditions:
1. Altitude: ≤ 1000m (must using other different designs if >1000m)
2. Wind pressure: ≤ 70Pa (=35m/s)
3. Humidity: daily average ≤ 95%, monthly average ≤ 90%
4. Ambient temperature: +40℃ ~ -25℃
5. Shockproof level: horizontal acceleration 0.4/S, vertical acceleration 0.15m/s
6. Earthquake intensity: 8°
7. Gradient of installation site: ≤ 3°
8. Installation environment: no corrosive or flammable gas or vapor, and no severe vibration
No.
|
Items
|
Units
|
Values
|
|
1
|
Rated Voltage
|
Primary Side
|
kV
|
12
|
Secondary Side
|
kV
|
0.4, 0.23
|
||
2
|
Rated Capacity
|
|
kVA
|
100, 125, 160, 200, 250, 315, 400, 500, 630, 800, 1000, 1250, 1600, 2000, 2500
|
3
|
No-Load Voltage Regulation
|
|
|
±2×2.5%
|
4
|
Connection Mode
|
|
|
△/Yn11
|
5
|
Rated Insulation Level
|
Lightning Impulse Withstand Voltage (Full Wave, Peak)
|
kV
|
75
|
1min Power Frequency Withstand Voltage
|
kV
|
35
|
||
6
|
Power Frequency Withstand Voltage on Low Voltage Side
Phase to Phase and Phase to Ground (1min) |
Major Loop
|
kV
|
2.5
|
Control and Measuring Loop
|
kV
|
2.0
|
||
7
|
Acoustic Level
|
|
dB
|
50
|
8
|
IP Code
|
|
|
IP34
|
9
|
Cooling Mode
|
|
|
ONAN
|