Products and Services
Working conditions:
1. Ambient temperature: +40℃~-15℃
2. Humidity: average daily humidity≤95%, average daily vapor pressure≤2.2Kpa, average monthly humidity≤90%, average monthly vapor pressure≤1.8Kpa
3. Altitude: ≤3000m
4. Earthquake intensity: ≤8°
5. No corrosive or inflammable gas or vapor
6. No frequent severe vibration
Items | Units | Values | ||
Rated Voltage | kV | 3.6,7.2,12 | ||
Rated Frequency | Hz | 50 | ||
Rated Current of Circuit Breaker | A | 630, 1250, 1600, 2000, 2500, 3150 | ||
Rated Current of Switchgear | A | 630, 1250, 1600, 2000, 2500, 3150 | ||
Rated Short Time Withstand Current (4S) | kA | 16, 20, 25, 31.5, 40 | ||
Rated Peak Withstand Current (Peak) | kA | 40, 50, 63, 80, 100 | ||
Rated Short Circuit Breaking Current | kA | 16, 20, 25, 31.5, 40 | ||
Rated Short Circuit Making Current (Peak) | kA | 40, 50, 63, 80, 100 | ||
Rated Insulation Level | 1min Power Frequency Withstand Voltage | Phase to Phase, Phase to Ground | kV | 24, 32, 42 |
Breaking | kV | 24, 32, 48 | ||
Lightning Impulse Withstand Voltage (Peak) | Phase to Phase, Phase to Ground | kV | 40, 60, 75 | |
Breaking | kV | 46, 70, 80 | ||
IP Code | kV | Outer Shell: IP4X, Compartments and Circuit Breaker Chamber Door: IP2X |