Products and Services
Working Conditions:
1. Altitude: ≤2000m
2. Ambient temperature: -5°C ~ +40°C; average daily temperature: ≤ +35°C
3. Relative humidity: ≤50% when it is +40°C; higher humidity is allowed upon lower temperature (i.e., 90% humidity at +20°C)
4. No potential of fire hazard or explosion; no severe pollution, chemical corrosion or severe vibration
5. Gradient: ≤5°
6. Applicable for short time (not more than 24h) transportation and storage at -25°C~+55°C
Technical Parameters:
1. Rated working voltage: 380V, 660V
2. Rated voltage of auxiliary circuit: AC220V, 380V, DC110V, 220V
3. Frequency: 50Hz~60Hz
4. Rated current: horizontal busbar≤3150A, vertical busbar: 630A, 800A, 1200A
5. Rated short time withstand current: 50, 50kA/1s; neutral busbar: 30kA/1s
6. Rated peak current: 105kA/0.1s, 50kA/0.1s
7. Functional unit (drawer) breaking capacity:50kA (valid value)
8. Outer shell IP code: IP30, IP40
9. Busbar arrangement: 3-phase 4-wire system, 3-phase 5-wire system
10. Operation mode: local, remote and automatic operations