Products and Services
Features:
JP series cabinet has 3 basic functions: power distribution, compensation and measurement. Clients can select from the following schemes:
01 - power distribution + compensation + measurement
02 - power distribution + compensation
03 - power distribution + measurement
04 - compensation + measurement
05 - power distribution
06 - measurement
07 - compensation
Performance:
1. Quick response, nice compensation effect, reliable operation, and optional function of earthing leakage protection
2. Protection function: overvoltage, overload, undervoltage, undercurrent, short circuit, loss of phase, and zero sequence ultra-limit
3. Automatic operation function: automatic recovery within 10s after power off and power on
4. Power factor of the grid increasing to above 0.95
Operation Conditions:
1. Ambient temperature: -40℃~+55℃
2. Relative humidity: ≤90% (relative ambient temperature 20℃~25℃)
3. Altitude: ≤3000m
4. Installed in the cabinet; no potential of fire hazard or explosion; no severe pollution, chemical corrosion or severe vibration
5. Gradient: ≤5°
Technical Parameters:
1. Rated voltage: 400V
2. Rated frequency: 50Hz
3. Capacity of transformer: 10, 20, 30, 50, 63, 80, 100, 125, 160, 200, 250, 315, 400, 500, 630(kVA)
4. Capacitor grouping: grade 2, 3, 4, 5 (special grouping is acceptable upon clients demands)
5. Feeder circuit: 2 circuits and each circuit configured with 80% ~ 100% of the total capacity of transformer; special requirement is acceptable upon clients demands
6. Compensation mode: cycle switchover, coding switchover, fuzzy control automatic switchover
7. Control physical quantity: reactive power or reactive current
8. Quickest response time: ≤20ms