XNKBS01 Outdoor Packaged Sub-Section Post


Sub-section post takes the switching function, to distribute power and link the power source and distribution network. It is the extension of power source busbar, which increases the number of power source. The application of sub-section post solves several problems, such as lack of outgoing lines of substation and restriction of outgoing line corridor. It reduces the investment and upgrades the structure of power grid.

Product introduction


Working Conditions:
1. Altitude: ≤1000m
2. Maximum ambient temperature: + 40℃
3. Minimum ambient temperature: -25℃
4. Maximum daily temperature difference: 25K
5. Indoor humidity: daily average ≤95%, monthly average ≤90%
6. Earthquake resistance: horizontal acceleration 0.2g, vertical acceleration 0.1g, applied simultaneously; using resonance, sine and beat wave test method; exciting 5 times every 2s, 5 waves per time, safety factor ≥1.67
7. No gas, vapor, chemical deposit, dust or pollution that might affect the insulation of load switch; no explosive or corrosive medium
8. Applicable for unearthed system, or 10kV system earthed through low resistance or arc suppression coil

 

Technical Parameters:

No. Items Units Values
Load Switch Combined Devices
1 Rated Voltage kV 12
2 Rated Frequency Hz 50
3 Rated Current A 630 200
4 Rated Load Breaking Current A 630 630
5 Rated Short Time Withstand Current (Valid Value) kA 20kA
6 Rated Short Circuit Duration Time s 3s
7 Rated Peak Withstand Current kA 50 / 63
8 Closed Loop Breaking Current A 630
9 Rated Cable Charging Breaking Current A 25
10 Rated No-Load Transformer Breaking Current A 16
11 Rated Breaking Transfer Current A   1750
12  Prospective Short Circuit Breaking Current of Fuse Protector (Valid Value) kA   63
13 Earthing Switch Short Time Withstand Current /Duration Time kA 25kA/1s
14 Rated Current Breaking Times Number of Times ≥200
15 Mechanical Life Number of Times ≥2000
16 Annual Leak Rate of SF6 Gas   ≤1%
17 1min Power Frequency Withstand Voltage (Valid Value) Breaking kV 48
Phase to Phase kV 42
Phase to Ground kV 42
Lightning Impulse Withstand Voltage (Peak Value) Breaking kV 85
Phase to Phase kV 75
Phase to Ground kV 75
18 Spring Operating Mechanism   Manual, or upgraded to electric
19 Operating Voltage V DC 48V/ AC 220V
21 External Insulation Creepage Distance mm/kV ≥20
22 Non-Simultaneity While Opening ms <5
23 Non-Simultaneity While Closing ms <5
24 Major Loop Resistance <140
25 IP Code of Cabinet Shell   IP4X