Working Conditions:
1. Altitude: ≤1000m
2. Maximum ambient temperature: + 40℃
3. Minimum ambient temperature: -25℃
4. Maximum daily temperature difference: 25K
5. Indoor humidity: daily average ≤95%, monthly average ≤90%
6. Earthquake resistance: horizontal acceleration 0.2g, vertical acceleration 0.1g, applied simultaneously; using resonance, sine and beat wave test method; exciting 5 times every 2s, 5 waves per time, safety factor ≥1.67
7. No gas, vapor, chemical deposit, dust or pollution that might affect the insulation of load switch; no explosive or corrosive medium
8. Applicable for unearthed system, or 10kV system earthed through low resistance or arc suppression coil
No. | Items | Units | Values | ||
Load Switch | Combined Devices | ||||
1 | Rated Voltage | kV | 12 | ||
2 | Rated Frequency | Hz | 50 | ||
3 | Rated Current | A | 630 | 200 | |
4 | Rated Load Breaking Current | A | 630 | 630 | |
5 | Rated Short Time Withstand Current (Valid Value) | kA | 20kA | ||
6 | Rated Short Circuit Duration Time | s | 3s | ||
7 | Rated Peak Withstand Current | kA | 50 / 63 | ||
8 | Closed Loop Breaking Current | A | 630 | ||
9 | Rated Cable Charging Breaking Current | A | 25 | ||
10 | Rated No-Load Transformer Breaking Current | A | 16 | ||
11 | Rated Breaking Transfer Current | A | 1750 | ||
12 | Prospective Short Circuit Breaking Current of Fuse Protector (Valid Value) | kA | 63 | ||
13 | Earthing Switch Short Time Withstand Current /Duration Time | kA | 25kA/1s | ||
14 | Rated Current Breaking Times | Number of Times | ≥200 | ||
15 | Mechanical Life | Number of Times | ≥2000 | ||
16 | Annual Leak Rate of SF6 Gas | ≤1% | |||
17 | 1min Power Frequency Withstand Voltage (Valid Value) | Breaking | kV | 48 | |
Phase to Phase | kV | 42 | |||
Phase to Ground | kV | 42 | |||
Lightning Impulse Withstand Voltage (Peak Value) | Breaking | kV | 85 | ||
Phase to Phase | kV | 75 | |||
Phase to Ground | kV | 75 | |||
18 | Spring Operating Mechanism | Manual, or upgraded to electric | |||
19 | Operating Voltage | V | DC 48V/ AC 220V | ||
21 | External Insulation Creepage Distance | mm/kV | ≥20 | ||
22 | Non-Simultaneity While Opening | ms | <5 | ||
23 | Non-Simultaneity While Closing | ms | <5 | ||
24 | Major Loop Resistance | uΩ | <140 | ||
25 | IP Code of Cabinet Shell | IP4X |