Products and Services
Working conditions:
1. Surrounding air temperature: +40℃~-5℃; 24h average temperature: not higher than +35℃
2. Altitude: not higher than 2000m
3. Relative humidity: not higher than 50% at +40℃; higher humidity allowed if lower temperature; maximum average humidity of the most humid month: 90%, minimum average temperature of this month: +25℃, and taking into consideration of condensation on the surface of products because of temperature change
4. Pollution grade: III
5. Installation category: if rated working voltage is 660V and below, installation category is IV; if rated working voltage is 380V, the installation category of auxiliary circuit is III (except that the installation category of undervoltage tripper coils and power transformer primary coils are the same with that of the main circuit coils)
Frame Size Rated Current (Inm) (A)
|
Rated Current (ln) (A)
|
2000
|
(400), 630, 800, 1000, 1250, 1600, 2000
|
3200
|
2000, 2500, 3200
|
6300
|
4000, 5000, 6300
|
Frame Size Rated Current (Inm) (A)
|
Item
|
380V
|
660V
|
Remark
|
2000A/3200A
4000A/6300A |
Rated Ultimate Short Circuit Breaking Capacity (lcu) kA
|
65/80
100/120 |
50/65
75/75 |
cosɸ=0.2 at 380V; cosɸ=0.25 at 660V
|
Rated Service Short Circuit Breaking Capacity (lcs) kA
|
40/50
80/100 |
40/50
65/65 |
—
|
|
Rated Short Time Withstand Current (Icw) kA
|
40/65
80/100 |
40/50
65/65 |
1s, delay 0.4s
|
Long Delay
|
Short Delay
|
Instantaneous Time
|
Earthing Fault
|
|||
Ir1
|
Ir2
|
Deviation
|
Ir3
|
Deviation
|
Ir4
|
Deviation
|
(0.4~1) In (Minimum 160)
|
(0.4~15) In
|
±10%
|
1.0In~50kA +OFF
|
±15%
|
(0.2~0.8) (Maximum 1200A, minimum 160A)
|
±10%
|
1.05Ir1
|
1.3Ir1
|
1.5Ir1 Setting Time (S)
|
15
|
30
|
60
|
120
|
240
|
480
|
>2h No Operating
|
<1h Operating
|
2.01Ir1 Operating Time (S)
|
8.4
|
16.9
|
33.7
|
67.5
|
135
|
270
|
Current
|
Operating Time
|
|||||
I≥Ir2 I≤8Ir1
|
Inverse Time
|
I2T=(8Ir1)2ts
|
||||
I≥Ir2 I>8Ir1
|
Definite Time
|
Stable Time
|
0.1
|
0.2
|
0.3
|
0.4
|