型号
|
SDKW1L-100
|
SDKW1L-225
|
SDKW1L-400
|
SDKW1L-630、800
|
|||||||||||
壳架电流Inm(A)
|
100
|
225
|
400
|
630, 800
|
|||||||||||
额定电流In(A)
|
10, 16, 20, 25, 32
|
100, 125, 140, 160
|
225, 315
|
400, 500, 630
|
|||||||||||
40, 50, 63, 80, 100
|
180, 200, 225
|
350, 400
|
700, 800
|
||||||||||||
极数
|
2
|
3
|
4
|
2
|
3
|
4
|
3
|
4
|
3
|
4
|
|||||
额定绝缘电压Ui(V)
|
AC800
|
||||||||||||||
额定工作电压Ue(V)
|
AC400
|
||||||||||||||
额定冲击耐受电压Uimp(V)
|
8000
|
||||||||||||||
飞狐距离
|
50
|
100
|
|||||||||||||
分断能力级别
|
L
|
M
|
H
|
L
|
M
|
H
|
L
|
M
|
H
|
L
|
M
|
H
|
|||
极限短路分断能力Icu(kA)
|
30
|
50
|
85
|
30
|
50
|
85
|
50
|
65
|
100
|
50
|
65
|
100
|
|||
运行短路分断能力Ics(kA)
|
15
|
35
|
50
|
15
|
35
|
50
|
35
|
42
|
65
|
35
|
42
|
65
|
|||
额定剩余短路接通(分断)能力
|
8.75
|
12.5
|
21
|
8.75
|
12.5
|
21
|
12.5
|
13.5
|
25
|
12.5
|
13.5
|
25
|
|||
额定剩余动作电流I△n(mA)
|
非延时型
|
30/100/500, 100/300/500
|
30/100/500, 100/300/500
|
100/300/500
|
300/500/1000
|
||||||||||
延时型
|
100/300/500
|
100/300/500
|
100/300/500
|
300/500/1000
|
|||||||||||
额定剩余不动作电流I△n(mA)
|
1/21△n
|
1/21△n
|
1/21△n
|
1/21△n
|
|||||||||||
操作性能(次)
|
通电
|
1500
|
1000
|
1000
|
1000
|
||||||||||
不通电
|
8500
|
7000
|
4000
|
4000
|
|||||||||||
总次数
|
10000
|
80000
|
5000
|
5000
|
|||||||||||
剩余电流保护动作时间
|
I△n
|
2I△n
|
5I△n
|
10I△n
|
|||||||||||
最大分断时间(S)
|
非延时型
|
0.2
|
0.1
|
0.04
|
0.04
|
||||||||||
延时型
|
0.5/1.15/2.15
|
0.35/1/2
|
0.25/0.9/1.9
|
0.25/0.9/1.9
|