Products and Services
Working Conditions:
1. Altitude: <2000m
2. Ambient temperature: -5℃~+40℃
3. Resistant to moist air
4. Resistant to salt mist and oil mist
5. Installation category of the main circuit is III, that of auxiliary circuit and control circuit is II
6. Relative humidity not higher than 50% when the highest temperature is +40℃; higher humidity allowed if lower temperature; taking special measures if temperature change occasionally brings about condensation.
7. Maximum gradient: 22.5°
8. No explosion potential, and no gas or conducting dust that can corrode metals and destroy insulation.
Controller Type
|
Basic Type
|
Intelligent Communication Type, Programming Communication Type, Liquid Crystal Type
|
|
Current
|
Operating Time
|
||
1.05Ir1
|
No Operating in 2h
|
||
13Ir1
|
Operating if ≤1h
|
||
2Ir1
|
Inm=100A, 225A Setting Value t1 (S)
|
t1=(12, 60, 80, 100)s
|
12s-100s (Maximum Stepping 1s)
|
Inm=400A, 630A, 800A Setting Value t1 (S)
|
t1=(12, 60, 100, 150)s
|
12s-100s (Maximum Stepping 1s)
|
|
Thermal Memory
|
30min, and Memory Removed if Power Failure (Optional Function for Intelligent Communication Type and Programming Communication Type)
|
||
|
1. Operating Time in Conformity with “I2T1=(2Ir1)2t1(1.2Ir1≤I
|
Current
|
Operating Time
|
|||||
Ir2≤I<1.5Ir2
|
Inverse Time
|
I2T1=(1.5Ir2)2t2
|
||||
1.5Ir2≤I
|
Definite Time
|
Setting Time t2(S)
|
0.06
|
0.01
|
0.2
|
0.3
|
Allowed Deviation (S)
|
±0.02
|
±0.03
|
±0.04
|
±0.06
|
||
Returnable Time (S)
|
|
|
0.14
|
0.21
|
Rated Current
|
100, 225
|
400, 630
|
800
|
Setting Current
|
Ir3=(4, 6, 7, 8, 10, 11, 12, 13, 14, 16) x Ir1
|
Ir3=(4, 6, 7, 8, 9, 10, 11, 12, 13, 14) x Ir1
|
Ir3=(4, 5, 6, 7, 8, 9, 10, 11, 12) x Ir1
|
Operating Characteristic
|
|
I≤0.85Ir3: No Operating
I≥1.15Ir3: Operating |
|